2 analog setpoints via terminal, Analog setpoints via terminal, Function library – Lenze E82xVxxxKxxxxx User Manual
Page 298

Function library
Configuration of analog and digital setpoints and actual values
Analog setpoints via terminal
l
298
EDS82EV903 EN 3.0
10.7.2
Analog setpoints via terminal
Description
Selection and adjustment of analog signals via terminal as setpoint or actual value.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0034
*
v
uSEr
Range of
setpoint
selection
Standard I/O
(X3/8)
Observe switch position of the
function module!
^ 298
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
2
Bipolar voltage −10 V ... +10 V
l
Minimum output frequency
(C0010) not effective
l
Individually adjust offset and
gain
3
Current 4 ... 20 mA open−circuit
monitored
TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.
C0034
*
v
(A)
uSEr
Range of
setpoint
selection
Application I/O
Observe jumper position of the
function module!
^ 298
1 X3/1U, X3/1I
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
2 X3/2U, X3/2I
1
Bipolar voltage −10 V ... +10 V
Minimum output frequency
(C0010) not effective
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
4
Current 4 ... 20 mA open−circuit
monitored
Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA
C0026
*
Offset for
analog input 1
(AIN1–OFFSET)
0.0
−200.0
{0.1 %}
200.0
l
Setting for X3/8 or X3/1U,
X3/1I
l
The upper limit of the setpoint
range from C0034 corresponds
to 100 %
l
C0026 and C0413/1 are equal
^ 298
C0027
*
Gain for analog
input 1
(AIN1−GAIN)
100.0 −1500.0
{0.1 %}
1500.0
l
Setting for X3/8 or X3/1U,
X3/1I
l
100.0 % = gain 1
l
Inverted setpoint selection
through negative gain and
negative offset
l
C0027 and C0414/1 are equal
^ 298