Function library – Lenze E82xVxxxKxxxxx User Manual
Page 299

Function library
Configuration of analog and digital setpoints and actual values
Analog setpoints via terminal
l
299
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0413
*
Offset − analog
inputs
−200.0
{0.1 %}
200.0 The upper limit of the setpoint
range from C0034 corresponds to
100 %
^ 298
1 AIN1−OFFSET
0.0
Setting for X3/8 or X3/1U, X3/1I
C0413/1 and C0026 are the same
2 AIN2−OFFSET
0.0
Setting for X3/2U, X3/2I
(only application I/O)
C0414
*
Gain − analog
inputs
−1500.0
{0.1 %}
1500.0
l
100.0 % = gain 1
l
Inverted setpoint selection
through negative gain and
negative offset
1 AIN1−GAIN
100.0
Setting for X3/8 or X3/1U, X3/1I
C0414/1 and C0027 are the same
2 AIN2−GAIN
100.0
Setting for X3/2U, X3/2I
(only application I/O)
C0430
*
v
(A)
Automatic
adjustment of
analog inputs
0
0
Inactive
The gain and offset are calculated
by entering two points of the
setpoint characteristic. Enter
points that are as far away from
each other as possible for high
accuracy of calculation:
1. In C0430, select the input the
gain and the offset are to be
calculated for
2. In C0431, enter the X value
(setpoint) and the Y value
(output frequency) of point 1
3. In C0432, enter the X value
(setpoint) and the Y value
(output frequency) of point 2
4. Calculated values are
automatically entered in C0413
(offset) and C0414 (gain)
^ 298
1
Entry of points for X3/1U, X3/1I
2
Entry of points for X3/2U, X3/2I
C0431
*
v
(A)
Coordinates of
point 1
−100.0
{0.1 %}
100.0
1 X (P1)
−100.0 Analog setpoint of P1
100 % = max. input value (5 V, 10 V or 20 mA)
2 Y (P1)
−100.0 Output frequency of P1
100 % = C0011
C0432
*
v
(A)
Coordinates of
point 2
−100.0
{0.1 %}
100.0
1 X (P2)
100.0 Analog setpoint of P2
100 % = max. input value (5 V, 10 V or 20 mA)
2 Y (P2)
100.0 Output frequency of P2
100 % = C0011