Technical data – Lenze E82xVxxxKxxxxx User Manual
Page 57

Technical data
Operation with increased rated power
Rated data for 400 V mains voltage
l
57
EDS82EV903 EN 3.0
Typical motor power −
three−phase asynchronous
motor (4−pole)
P
rated
[kW]
22
30
37
P
rated
[hp]
30
40
50
8200 vector type
With mains filter
E82xV153K4B3xx
E82xV223K4B3xx
−
Without mains filter
E82xV153K4B2xx
2)
E82xV223K4B2xx
2)
E82xV303K4B2xx
2)
3)
Rated mains current
without mains choke/mains
filter
I
mains
[A]
−
−
−
With mains choke/mains filter
I
mains
[A]
39
50
60
Output power +U
DC
, −U
DC
1)
P
DCres
[kW]
10.2
4
0
Rated output
current at
switching
frequency
1 kHz sin
I
r
[A]
32
47
59
2 kHz sin
4 kHz sin
1 kHz
I
r
[A]
43
56
66
2 kHz
4 kHz
Max. permissible
output current for
60 s at switching
frequency
1 kHz sin
I
max
[A]
48
70.5
89
2 kHz sin
4 kHz sin
1 kHz
I
max
[A]
48
70.5
89
2 kHz
4 kHz
Power loss (operation with I
N24
)
E82EV...
P
loss
[W]
430
640
810
E82DV... inside/outside
P
loss
[W]
143/287
213/427
270/540
E82CV... inside/cooler
P
loss
[W]
143/287
213/427
−
Dimensions
Dependent on the mounting variant (
^ 61)
Mass with mains
filter
E82EV...
m [kg]
34
34
E82DV...
m [kg]
34
34
E82CV...
m [kg]
Separate mains filter
−
Mass without
mains filter
E82EV...
m [kg]
15
E82DV...
m [kg]
15
E82CV...
m [kg]
13
−
1)
Power supplied by the DC bus when operating with power−adapted motor
2)
Operation only permitted with mains choke (
^ 106)
3)
Max. permissible operating ambient temperature +35 °C