Function library, Code table – Lenze E82xVxxxKxxxxx User Manual
Page 388

Function library
Code table
l
388
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0034
*
v
uSEr
Range of
setpoint
selection
Standard I/O
(X3/8)
Observe switch position of the
function module!
^ 298
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
Current 0 ... 20 mA
1
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
2
Bipolar voltage −10 V ... +10 V
l
Minimum output frequency
(C0010) not effective
l
Individually adjust offset and
gain
3
Current 4 ... 20 mA open−circuit
monitored
TRIP Sd5 if I < 4 mA
Reversal of rotation direction only
possible with a digital signal.
C0034
*
v
(A)
uSEr
Range of
setpoint
selection
Application I/O
Observe jumper position of the
function module!
^ 298
1 X3/1U, X3/1I
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
2 X3/2U, X3/2I
1
Bipolar voltage −10 V ... +10 V
Minimum output frequency
(C0010) not effective
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
Reversal of rotation direction only
possible with a digital signal.
4
Current 4 ... 20 mA open−circuit
monitored
Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA
C0035
*
v
Operation
mode − DC
injection brake
(DCB)
0
0
Brake voltage selection under C0036
Hold time
ð C0107
^ 292
1
Brake current selection under C0036
C0036 Voltage/
current DC
injection brake
(DCB)
а
0.00
{0.01 %}
150.00 %
а
Device−dependent
l
Based on V
rated
, I
rated
l
Setting applies to all permitted
mains voltages
^ 292
C0037 JOG1
20.00 −650.00
{0.02
Hz}
650.00 JOG = fixed setpoint
Additional fixed setpoints
ðC0440
^ 309
C0038 JOG2
30.00 −650.00
{0.02
Hz}
650.00
C0039 JOG3
40.00 −650.00
{0.02
Hz}
650.00
C0040
*
v
Controller
inhibit (CINH)
−0−
Controller inhibited (CINH)
Controller can only be enabled if
X3/28 = HIGH
^ 277
−1−
Controller enabled (CINH)
C0043
*
v
TRIP reset
0
No current fault
Reset active fault with C0043 = 0
1
Fault active
C0044
*
Setpoint 2
(NSET1-N2)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
l
Selection if C0412/2 =
FIXED−FREE (not assigned)
l
Display if C0412/2 is linked to
a signal source
^ 311
C0046
*
Setpoint 1
(NSET1-N1)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
l
Selection if C0412/1 =
FIXED−FREE (not assigned)
l
Display if C0412/1 is linked to
a signal source
^ 311