Function library – Lenze E82xVxxxKxxxxx User Manual
Page 422

Function library
Code table
l
422
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0419
v
Free
configuration
of analog
outputs
Output of analog signals to terminal
^ 332
1 X3/62
(AOUT1−IN)
0
Output frequency
(MCTRL1−NOUT+SLIP)
A selection in C0111 is copied into
C0419/1. Change of C0419/1 sets
C0111 = 255!
2
(A)
X3/63
(AOUT2−IN)
2
Apparent motor current
(MCTRL1−IMOT)
3
(A)
X3/A4
(DFOUT1−IN)
3
DC−bus voltage (MCTRL1−DCVOLT)
Frequency output: 50 Hz ... 10 kHz
C0419
v
(Cont.)
Possible analog signals for C0419
^ 332
0
Output frequency
(MCTRL1−NOUT+SLIP)
6 V/12 mA/5.85 kHz
º C0011
1
Device utilisation (MCTRL1−MOUT) at
V/f characteristic control (C0014 = 2 or
3)
3 V/6 mA/2.925 kHz
º rated active
inverter current (active
current/C0091)
Actual motor torque (MCTRL1−MACT)
with vector control (C0014 = 4) or
sensorless torque control (C0014 = 5)
3 V/6 mA/2.925 kHz
º rated
motor torque
2
Apparent motor current
(MCTRL1−IMOT)
3 V/6 mA/2.925 kHz
º rated
inverter current
3
DC−bus voltage (MCTRL1−DCVOLT)
6 V/12 mA/5.85 kHz
º DC 1000 V
(400 V mains)
6 V/12 mA/5.85 kHz
º DC 380 V
(230 V mains)
4
Motor power (MCTRL1−PMOT)
3 V/6 mA/2.925 kHz
º rated
motor power
5
Motor voltage (MCTRL1−VOLT)
4.8 V/9.6 mA/4.68 kHz
ºrated
motor voltage
6
1/output frequency (1/C0050)
(MCTRL1−1/NOUT)
2 V/4 mA/1.95 kHz
º 0.5 ´ C0011
7
Output frequency within adjusted
limits (DCTRL1−C0010...C0011)
0 V/0 mA/4 mA/0 kHz
º f = f
min
(C0010)
6 V/12 mA/5.85 kHz
º f = f
max
(C0011)
8
Operation with process controller
(C0238 = 0, 1):
Actual process controller value
(PCTRL1−ACT)
6 V/12 mA/5.85 kHz
º C0011
Operation without process controller
(C0238 = 2):
Output frequency without slip
(MCTRL1−NOUT)