Function library – Lenze E82xVxxxKxxxxx User Manual
Page 363

Function library
Display of operating data, diagnostics
Display of operating data
l
363
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0050
*
uSEr
Output freq.
(MCTRL1−
NOUT)
−650.00
{Hz}
650.00 Read only: Output frequency
without slip compensation
C0051
*
Output freq.
with slip
compensation
(MCTRL1−NOUT
+SLIP) or
Actual process
controller
value
(PCTRL1−ACT)
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
During operation without process
controller (C0238 = 2):
l
Read only: output frequency
with slip compensation
(MCTRL1−NOUT+SLIP)
During operation with process
controller (C0238 = 0, 1):
l
Selection if C0412/5 =
FIXED−FREE (not assigned)
l
Display if C0412/5 is linked to
a signal source
^ 324
C0052
*
Motor voltage
(MCTRL1−VOLT)
0
{V}
1000 Read only
C0053
*
DC−bus voltage
(MCTRL1−
DCVOLT)
0
{V}
1000 Read only
C0054
*
Apparent
motor current
(MCTRL1−
IMOT)
0.0
{A}
2000.0 Read only
C0056
*
Device
utilisation
(MCTRL1−
MOUT)
−255
{%}
255 Read only
The display value for the "Vector
control" or "Sensorless torque
control" operating mode can be
changed in C0311.
C0061
*
Heatsink
temperature
0
{
°C}
255 Read only
l
If the heatsink temperature
>
J
max
− 5 °C:
– Warning OH is provided
– Switching frequency is
reduced to 4 kHz if C0144 = 1
l
If the heatsink temperature
>
J
max
:
– Controller sets TRIP OH
C0138
*
Process
controller
setpoint 1
(PCTRL1−SET1)
0.00
−650.00
{0.02
Hz}
650.00 The set value will be lost during
mains switching!
l
Selection if C0412/4 =
FIXED−FREE
l
Display if C0412/4
¹
FIXED−FREE
^ 322
C0189
*
(A)
Output signal −
follow−up
controller
(PCTRL1−FOLL1−
OUT)
−650.00
{0.02
Hz}
650.00 Read only
Follow−up controller =
PCTRL1−FOLL1
C0320
(A)
Actual process
controller value
(PCTRL1−ACT)
−650.00
{0.02
Hz}
650.00 Read only
C0321
(A)
Process
controller
setpoint
(PCTRL1−SET)
−650.00
{0.02
Hz}
650.00 Read only