Technical data – Lenze E82xVxxxKxxxxx User Manual
Page 59

Technical data
Operation with increased rated power
Rated data for 400 V mains voltage
l
59
EDS82EV903 EN 3.0
Typical motor power
Three−phase asynchronous
motor (4−pole)
P
rated
[kW]
90
110
P
rated
[hp]
125
150
8200 vector type
With mains filter
E82xV753K4B3xx
−
Without mains filter
E82xV753K4B2xx
2)
E82xV903K4B2xx
2)
3)
Rated mains current
without mains choke/mains
filter
I
mains
[A]
−
−
With mains choke/mains filter
I
mains
[A]
144
185
Output power +U
DC
, −U
DC
1)
P
DCres
[kW]
28.1
40.8
Rated output
current at
switching
frequency
1 kHz sin
I
r
[A]
150
159
4)
2 kHz sin
4 kHz sin
1 kHz
I
r
[A]
159
205
2 kHz
4 kHz
Max. permissible
output current for
60 s at switching
frequency
1 kHz sin
I
max
[A]
225
238
4)
2 kHz sin
4 kHz sin
1 kHz
I
max
[A]
225
270
2 kHz
4 kHz
Power loss (operation with I
N8
)
E82EV...
P
loss
[W]
1960
2400
E82DV... inside/outside
P
loss
[W]
653/1307
800/1600
E82VV... inside/cooler
P
loss
[W]
−
−
Dimensions
Dependent on the mounting variant (
^ 61)
Mass with mains
filter
E82EV...
m [kg]
112
E82DV...
m [kg]
112
E82CV...
m [kg]
−
Mass without
mains filter
E82EV...
m [kg]
59
E82DV...
m [kg]
59
E82CV...
m [kg]
−
1)
Power supplied by the DC bus when operating with power−adapted motor
2)
Operation only permitted with mains choke (
^ 106)
3)
Max. permissible operating ambient temperature +35 °C
4)
Only operate with automatic switching frequency reduction (C144 = 1). Ensure that the specified current values are
not exceeded.