Electrical installation – Lenze E82xVxxxKxxxxx User Manual
Page 164

Electrical installation
Standard devices in the power range 75 ... 90 kW
Connection relay outputs K1 and K2
l
164
EDS82EV903 EN 3.0
Relay K2
Function
Relay position
switched
Message
(Lenze setting)
Technical data
X1.3/K21
Relay output
normally−closed
contact
opened
not assigned
AC 250 V/3 A
DC 24 V/2 A ... DC 240 V/0.22 A
X1.3/K22
Relay mid−position
contact
X1.3/K24
Relay output
normally−open
contact
closed
not assigned
PES
HF shield termination by PE connection through shield clamp
)
Note!
ƒ
Switching of control signals:
– Use shielded cables
– HF shield termination by PE connection
– The minimum load for switching the signals through correctly is 12 V and
5 mA. Both values have to be exceeded at the same time.
ƒ
Switching of mains potentials:
– Unshielded cables are sufficient
ƒ
For the protection of the relay contacts a corresponding suppressor circuit is
absolutely required for an inductive or a capacitive load!
ƒ
The service life of the relay depends on the type of load (ohmic, inductive or
capacitive) and the value of the switching capacity.
ƒ
The output message can be changed with C0409.
ƒ
If you use an application I/O function module:
– The relay K2 is only active with application I/O E82ZAFAC from version
Vx21 onwards.