Function library – Lenze E82xVxxxKxxxxx User Manual
Page 310

Function library
Configuration of analog and digital setpoints and actual values
Setpoints via fixed setpoints (JOG)
l
310
EDS82EV903 EN 3.0
Active setpoint
Level at
NSET1−JOG1/3
NSET1−JOG2/3
Other setpoint source
LOW
LOW
JOG 1
HIGH
LOW
JOG 2
LOW
HIGH
JOG 3
HIGH
HIGH
)
Note!
In addition to the free configuration in C0410 you can also use the fixed
assignment in C0007 to link the function to digital inputs.
Operation with application I/O
ƒ
In C0410/1, link the NSET1−JOG1/3/5 signal to a digital input signal.
ƒ
In C0410/2, link the NSET1−JOG2/3/6/7 signal to a digital input signal.
ƒ
In C0410/33, link the NSET1−JOG4/5/6/7 signal to a digital input signal.
Active setpoint
Level at
NSET1−JOG1/3/5/7
NSET1−JOG2/3/6/7
NSET1−JOG4/5/6/7
Other setpoint source
LOW
LOW
LOW
JOG 1
HIGH
LOW
LOW
JOG 2
LOW
HIGH
LOW
JOG 3
HIGH
HIGH
LOW
JOG 4
LOW
LOW
HIGH
JOG 5
HIGH
LOW
HIGH
JOG 6
LOW
HIGH
HIGH
JOG 7
HIGH
HIGH
HIGH
Influence on other setpoints
ƒ
The maximum output frequency (C0011) also limits the fixed setpoints (JOG).
ƒ
The minimum output frequency (C0010) does not limit the fixed setpoints (JOG).
ƒ
Fixed setpoints (JOG) have priority over analog setpoint 1 (NSET1−N1) and analog
setpoint 2 (NSET1−N2).
ƒ
The additional setpoint (PCTRL1−NADD) acts additively on the fixed setpoints.
Setting tips
The display of the parameter can be related to a process variable. (
^ 362