Commissioning, Important codes for quick commissioning – Lenze E82xVxxxKxxxxx User Manual
Page 218

Commissioning
Important codes for quick commissioning
l
218
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0007
v
uSEr
(Cont.)
E4
E3
E2
E1
31
DCB
QSP
PCTRL1−I−
OFF
DFIN1−ON
32
TRIP−Set
QSP
PCTRL1−I−
OFF
DFIN1−ON
33
QSP
PAR
PCTRL1−
OFF
DFIN1−ON
34
CW/QSP
CCW/QSP
PCTRL1−I−
OFF
DFIN1−ON
35
JOG2/3
JOG1/3
PAR
DFIN1−ON
36
DCB
QSP
PAR
DFIN1−ON
37
JOG1/3
QSP
PAR
DFIN1−ON
38
JOG1/3
PAR
TRIP−Set
DFIN1−ON
39
JOG2/3
JOG1/3
TRIP−Set
DFIN1−ON
40
JOG1/3
QSP
TRIP−Set
DFIN1−ON
C0007
v
uSEr
(Cont.)
E4
E3
E2
E1
41
JOG1/3
DCB
TRIP−Set
DFIN1−ON
42
QSP
DCB
TRIP−Set
DFIN1−ON
43
CW/CCW
QSP
TRIP−Set
DFIN1−ON
44
UP
DOWN
PAR
DFIN1−ON
45
CW/CCW
QSP
PAR
DFIN1−ON
46
H/Re
PAR
QSP
JOG1/3
47
CW/QSP
CCW/QSP
H/Re
JOG1/3
48
PCTRL1−
OFF
DCB
PCTRL1−I−
OFF
DFIN1−ON
49
PCTRL1−
OFF
JOG1/3
QSP
DFIN1−ON
50
PCTRL1−
OFF
JOG1/3
PCTRL1−I−
OFF
DFIN1−ON
51
DCB
PAR
PCTRL1−I−
OFF
DFIN1−ON
255
Free configuration in C0410
Read only
Do not change C0007 since
settings in C0410 may get lost
C0010
uSEr
Minimum
output
frequency
0.00
0.00
à
14.5 Hz
{0.02
Hz}
650.00
l
C0010 not effective in the case
of bipolar setpoint selection
(−10 V ... + 10 V)
l
C0010 only limits the analog
input 1
l
In the case of a max. output
frequency > 50 Hz the
switching threshold of the auto
DCB in C0019 has to be
increased.
l
From software 3.5: If
C0010 > C0011, the drive does
not start when controller
enable is set.
à
Speed setting range 1 : 6 for
Lenze geared motors: For
operation with Lenze geared
motors has to be set
necessarily.
^ 281
C0011
uSEr
Maximum
output
frequency
50.00 7.50
à
87 Hz
{0.02
Hz}
650.00
C0012
uSEr
Acceleration
time main
setpoint
5.00
0.00
{0.02 s}
1300.00 Reference: frequency change 0 Hz
... C0011
l
Additional setpoint
ðC0220
l
Acceleration times that can be
activated via digital signals
ð
C0101
^ 286