Function library, Code table – Lenze E82xVxxxKxxxxx User Manual
Page 432

Function library
Code table
l
432
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0500
*
Calibration of
process
variable −
numerator
2000 1
{1}
25000
l
Codes C0010, C0011, C0017,
C0019, C0037, C0038, C0039,
C0044, C0046, C0049, C0050,
C0051, C0138, C0140, C0181,
C0239, C0625, C0626, C0627
can be calibrated in a way to
make the keypad display a
process variable
l
If C0500/C0501 are changed,
the "Hz" unit is not shown in
the display anymore
^ 362
C0501
*
Calibration of
process
variable −
denominator
10
1
{1}
25000
C0500
*
(A)
Calibration of
process
variable −
numerator
2000 1
{1}
25000
l
Codes C0037, C0038, C0039,
C0044, C0046, C0049, C0051,
C0138, C0140, C0181 can be
calibrated in a way to make the
keypad display a process
variable in the unit selected in
C0502
l
Frequency−dependent codes
such as C0010, C0011, C0017,
C0019, C0050, C0239, C0625,
C0626, C0627 are always
provided in "Hz"
l
Changes in codes C0500 and
C0501 affect codes C0010 and
C0011; their values are scaled
correspondingly in the process
^ 362
C0501
*
(A)
Calibration of
process
variable −
denominator
10
1
{1}
25000
C0502
*
(A)
Unit − process
variable
0
0: Ċ
1: ms
2: s
4: A
5: V
6: rpm
9: °C
10: Hz
11: kVA
12: Nm
13: %
14: kW
15: N
16: mV
17: m
W
18:
W
19: hex
34: m
35: h
42: mH
C0517
*
v
User menu
l
After mains switching or in the
g function the code from
C0517/1 is displayed.
l
In the Lenze setting the user
menu contains the most
important codes for
commissioning the operating
mode "V/f characteristic
control with a linear
characteristic"
l
If the password protection is
active, only the codes entered
in C0517 can be freely accessed
l
If less than 10 codes are
required, assign the value "0"
(zero) to the memory locations
not used. Please observe that
the software automatically
assigns code C0050 to a
memory location that is not
used, if it has not been
explicitly assigned to another
memory location.
^ 373
1 Memory 1
50
C0050
Output frequency (MCTRL1−NOUT)
2 Memory 2
34
C0034
Range of analog setpoint selection
3 Memory 3
7
C0007
Fixed configuration of digital input
signals
4 Memory 4
10
C0010
Minimum output frequency
5 Memory 5
11
C0011
Maximum output frequency
6 Memory 6
12
C0012
Acceleration time main setpoint
7 Memory 7
13
C0013
Deceleration time main setpoint
8 Memory 8
15
C0015
V/f rated frequency
9 Memory 9
16
C0016
V
min
boost
10 Memory 10
2
C0002
Parameter set transfer
Possible entries for C0517
xxxx
All codes apart from the codes labelled
with "(A)".
Syntax:
Codes: C0517/x = cccc
Subcodes: C0517/x = cccc.ss
C0518 Service codes
Alterations by Lenze service only!
C0519
C0520
C0597
*
v
Configuration −
motor phase
failure
detection
0
0
Inactive
1
TRIP error message
Keypad: LP1, bus: 32
2
Warning