Configuration of analog and digital setpoints and actual values
Setpoints via fixed setpoints (JOG)
l
309
EDS82EV903 EN 3.0
10.7.5
Setpoints via fixed setpoints (JOG)
Description
You can store up to three fixed setpoints per parameter set and retrieve them using digital
input signals.
At operation with application I/O 7 fixed setpoints are available per parameter set.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0037 JOG1
20.00 −650.00
{0.02
Hz}
650.00 JOG = fixed setpoint
Additional fixed setpoints
ðC0440
^ 309
C0038 JOG2
30.00 −650.00
{0.02
Hz}
650.00
C0039 JOG3
40.00 −650.00
{0.02
Hz}
650.00
C0440
(A)
Additional JOG
values
−650.00
{0.02
Hz}
650.00 JOG = fixed setpoint
Activation via configuration in
C0410
^ 309
1 JOG 1
20.00
C04401/1 and C0037 are the
same
2 JOG 2
30.00
C04401/2 and C0038 are the
same
3 JOG 3
40.00
C04401/3 and C0039 are the
same
4 JOG 4
15.00
5 JOG 5
25.00
6 JOG 6
35.00
7 JOG 7
45.00
Activation
Operation without application I/O
ƒ
In C0410/1, link the NSET1−JOG1/3 signal to a digital input signal.
ƒ
In C0410/2, link the NSET1−JOG2/3 signal to a digital input signal.