Technical data – Lenze E82xVxxxKxxxxx User Manual
Page 48

Technical data
Operation with rated power (normal operation)
Rated data for 500 V mains voltage
l
48
EDS82EV903 EN 3.0
Typical motor power −
three−phase asynchronous
motor (4−pole)
P
rated
[kW]
18.5
30
37
P
rated
[hp]
25
40
50
8200 vector type
With mains filter
E82xV153K4B3xx
E82xV223K4B3xx
E82xV303K4B3xx
Without mains filter
E82xV153K4B2xx
3)
E82xV223K4B2xx
3)
E82xV303K4B2xx
3)
Rated mains current at a
switching frequency of 8 kHz
(Lenze setting)
without mains choke/mains
filter
I
mains
[A]
43.5
−
−
With mains choke/mains filter
I
mains
[A]
29
42
55
Output power +U
DC
, −U
DC
1)
P
DCres
[kW]
11.8
4.6
0
Rated output
current at
switching
frequency
1 kHz sin
I
rated
[A]
5)
30.5
45
56
2 kHz sin
4 kHz sin
8 kHz sin
I
r
[A]
27
41
44
4)
16 kHz sin
2)
I
r
[A]
19
28
30
1 kHz
I
r
[A]
32
47
56
2 kHz
4 kHz
8 kHz
I
r
[A]
32
47
56
16 kHz
2)
I
r
[A]
22
33
41
Max. permissible
output current for
60 s at switching
frequency
1 kHz sin
I
max
[A]
46
66.5
65
2 kHz sin
4 kHz sin
8 kHz sin
I
max
[A]
41
61
65
4)
16 kHz sin
2)
I
max
[A]
29
42
45
1 kHz
I
max
[A]
48
70.5
84
2 kHz
4 kHz
8 kHz
I
max
[A]
48
70.5
84
16 kHz
2)
I
max
[A]
33
49
61
Power loss (operation with I
N8
)
E82EV...
P
loss
[W]
430
640
810
E82DV... inside/outside
P
loss
[W]
143/287
213/427
270/540
E82CV... inside/cooler
P
loss
[W]
−
−
−
Dimensions
Dependent on the mounting variant (
^ 61)
Mass with mains
filter
E82EV...
m [kg]
34
34
E82DV...
m [kg]
34
34
E82CV...
m [kg]
Separate mains filter
−
Mass without
mains filter
E82EV...
m [kg]
15
15
E82DV...
m [kg]
15
15
E82CV...
m [kg]
13
−
1)
Power supplied by the DC bus when operating with power−adapted motor
2)
Switching frequency is reduced to 4 kHz if
J reaches max. − 5 °C
3)
Operation only permitted with mains choke or mains filter (
^ 106)
4)
Only operate with automatic switching frequency reduction (C144 = 1). Ensure that the specified current values are
not exceeded.