Influence the process controller during operation, Function library – Lenze E82xVxxxKxxxxx User Manual
Page 325

Function library
Process controller
Influence the process controller during operation
l
325
EDS82EV903 EN 3.0
10.9.4
Influence the process controller during operation
Process controller switch−off (PCTRL1−OFF)
The process controller output does not send signals as long as this function is active.
Activation
The function must be linked with a digital input signal under C0410/19.
HIGH level at C0410/19 activates the function.
)
Note!
In addition to the free configuration under C0410 you can also use the fixed
assignment under C0007 to combine the function with a digital input.
Process controller stop (PCTRL1−STOP)
The process controller output is frozen on the current value when the function is activated.
The value remains unchanged until the function is deactivated.
Activation
The function must be linked with a digital input signal under C0410/21.
HIGH level at C0410/21 activates the function.
Integral action component switch−off (PCTRL1−I−OFF)
The process controller output provides the difference between setpoint and actual value,
if necessary with gain V
P
.
ƒ
Thus overcontrolled starting and stopping can be avoided. When the controller
operates normally, the integral action component K
I
can be connected.
ƒ
Application: e.g. dancer position control
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0184
*
Frequency
threshold
PCTRL1−I−OFF
0.0
0.0
{0.1 Hz}
25.0
l
If output frequency < C0184,
the I component of the process
controller is switched off
l
0.0 Hz = function inactive
^ 322
Activation
Link the function with a digital input signal in C0410/18.
HIGH level at C0410/18 activates the function.
)
Note!
In addition to the free configuration under C0410 you can also use the fixed
assignment under C0007 to combine the function with a digital input.