Function library – Lenze E82xVxxxKxxxxx User Manual
Page 364

Function library
Display of operating data, diagnostics
Display of operating data
l
364
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0322
(A)
Process
controller
output without
feedforward
control
(PCTRL1−OUT)
−650.00
{0.02
Hz}
650.00 Read only
C0323
(A)
Ramp function
generator
input
(NSET1−RFG1−
IN)
−650.00
{0.02
Hz}
650.00 Read only
C0324
(A)
Ramp function
generator
output
(NSET1−NOUT)
−650.00
{0.02
Hz}
650.00 Read only
C0325
(A)
PID controller
output
(PCTRL1−PID−
OUT)
−650.00
{0.02
Hz}
650.00 Read only
C0326
(A)
Process
controller
output
(PCTRL1−NOUT)
−650.00
{0.02
Hz}
650.00 Read only
C0500
*
Calibration of
process
variable −
numerator
2000 1
{1}
25000
l
Codes C0010, C0011, C0017,
C0019, C0037, C0038, C0039,
C0044, C0046, C0049, C0050,
C0051, C0138, C0140, C0181,
C0239, C0625, C0626, C0627
can be calibrated in a way to
make the keypad display a
process variable
l
If C0500/C0501 are changed,
the "Hz" unit is not shown in
the display anymore
^ 362
C0501
*
Calibration of
process
variable −
denominator
10
1
{1}
25000
C0500
*
(A)
Calibration of
process
variable −
numerator
2000 1
{1}
25000
l
Codes C0037, C0038, C0039,
C0044, C0046, C0049, C0051,
C0138, C0140, C0181 can be
calibrated in a way to make the
keypad display a process
variable in the unit selected in
C0502
l
Frequency−dependent codes
such as C0010, C0011, C0017,
C0019, C0050, C0239, C0625,
C0626, C0627 are always
provided in "Hz"
l
Changes in codes C0500 and
C0501 affect codes C0010 and
C0011; their values are scaled
correspondingly in the process
^ 362
C0501
*
(A)
Calibration of
process
variable −
denominator
10
1
{1}
25000
C0502
*
(A)
Unit − process
variable
0
0: Ċ
1: ms
2: s
4: A
5: V
6: rpm
9: °C
10: Hz
11: kVA
12: Nm
13: %
14: kW
15: N
16: mV
17: m
W
18:
W
19: hex
34: m
35: h
42: mH