Function library – Lenze E82xVxxxKxxxxx User Manual
Page 349

Function library
Free interconnection of digital signals
Free configuration of digital outputs
l
349
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0415
v
(Cont.)
Possible digital signals for C0415
^ 348
0
Not assigned (FIXED−FREE)
1
Parameter set 2 or parameter set 4 is
active (DCTRL1−PAR−B0)
PAR−B1 PAR−B0
LOW
LOW
LOW
HIGH
HIGH
LOW
HIGH
HIGH
Active
PAR1
PAR2
PAR3
PAR4
2
Pulse inhibit active (DCTRL1−IMP)
3
I
max
limit reached (MCTRL1−IMAX)
(C0014 = −5−: torque setpoint reached)
4
Frequency setpoint reached
(DCTRL1−RFG1=NOUT)
5
Ramp function generator 1: input =
output (NSET1−RFG1−I=O)
RFG1 = ramp function generator −
main setpoint
6
Values have fallen below frequency
threshold Q
min
(f < C0017)
(PCTRL1−QMIN)
LOW active
7
Output frequency = 0
(DCTRL1−NOUT=0)
8
Controller inhibit active (DCTRL1−CINH)
9...12
Reserved
13
Group signal
(DCTRL1−OH−PTC−LP1−FAN1−WARN):
Warning − overtemperature (
J
max
− 5
°C) (DCTRL1−OH−WARN)
or
Warning − motor overtemperature
(DCTRL1−LP1−PTC−WARN)
or
Set C0119 = 2 or C0119 = 5
Motor phase failure warning
(DCTRL1−LP1−WARN)
or
Set C0597 = 2
Warning − fan failure
(only active with 8200 motec)
With 8200 vector, C0608 must be
set to 0
14
DC bus overvoltage (DCTRL1−OV)
15
CCW rotation (DCTRL1−CCW)
16
Ready for operation (DCTRL1−RDY)
17
Parameter set 3 or parameter set 4
active (DCTRL1−PAR−B1)
PAR−B1 PAR−B0
LOW
LOW
LOW
HIGH
HIGH
LOW
HIGH
HIGH
Active
PAR1
PAR2
PAR3
PAR4
18
Values have fallen below TRIP or Q
min
or pulse inhibit (IMP) is active
(DCTRL1−TRIP−QMIN−IMP)
19
PTC warning (DCTRL1−PTC−WARN)
Set C0119 = 2 or C0119 = 5
Status of relay K
SR
Only with 8200 vector 15 ...90 kW,
variant "safe standstill":
HIGH = pulse inhibit active by
"safe standstill"
LOW = no pulse inhibit by "safe
standstill"