Function library
Free interconnection of analog signals
Free configuration of analog outputs
l
332
EDS82EV903 EN 3.0
10.11.2
Free configuration of analog outputs
Description
ƒ
The analog outputs (X3/62, X3/63) and the frequency output (X3/A4) can be freely
assigned to internal analog process signals or monitoring signals. The controller
outputs a voltage proportional to the internal signal at the analog outputs.
ƒ
Currents can also be output when using the application I/O.
– Range: 0 ... 20 mA, as of software version 1.1 also 4 ... 20 mA
– Setting via jumper at module and C0424
ƒ
A signal source can be assigned to several targets.
)
Note!
Use C0111 to permanently assign the analog output X3/62 to some internal
signal sources. C0419/1 is automatically adapted.
Codes for parameter setting
Code
Possible settings
IMPORTANT
No.
Name
Lenze Selection
C0419
v
Free
configuration
of analog
outputs
Output of analog signals to terminal
^ 332
1 X3/62
(AOUT1−IN)
0
Output frequency
(MCTRL1−NOUT+SLIP)
A selection in C0111 is copied into
C0419/1. Change of C0419/1 sets
C0111 = 255!
2
(A)
X3/63
(AOUT2−IN)
2
Apparent motor current
(MCTRL1−IMOT)
3
(A)
X3/A4
(DFOUT1−IN)
3
DC−bus voltage (MCTRL1−DCVOLT)
Frequency output: 50 Hz ... 10 kHz