Electrical installation, Operation at rated power – Lenze E82xVxxxKxxxxx User Manual
Page 128

Electrical installation
Standard devices in a power range from 0.25 ... 2.2 kW
Fuses and cable cross−sections according to UL
l
128
EDS82EV903 EN 3.0
Operation at rated power
8200 vector
Rated fuse current / cable cross−section
Fuse
Circuit−breaker
Type
L1, L2, L3, N, PE
Type
L1, L2, L3, N, PE
Type
[A]
[AWG]
[A]
[AWG]
Mains 1/N/PE AC 230/240 V − operation without mains choke/mains filter
E82xV251K2C
10
16
15
14
4)
E82xV371K2C
10
16
15
14
4)
E82xV551K2C
10
16
15
14
4)
E82xV751K2C
15
14
15
14
4)
E82xV152K2C
20
2 x 16
25
2 x 14
4)
E82xV222K2C
20
2 x 16
30
2 x 14
4)
Mains 1/N/PE AC 230/240 V − operation with mains choke/mains filter
E82xV251K2C
10
16
15
14
4)
E82xV371K2C
10
16
15
14
4)
E82xV551K2C
10
16
15
14
4)
E82xV751K2C
15
14
15
14
4)
E82xV152K2C
20
2 x 16
25
2 x 14
4)
E82xV222K2C
20
2 x 16
30
2 x 14
4)
Mains 3/PE AC 230/240 V − operation without mains choke/mains filter
E82xV551K2C
6
18
15
14
4)
E82xV751K2C
10
16
15
14
4)
E82xV152K2C
15
14
15
14
4)
E82xV222K2C
15
2 x 16
20
2 x 14
4)
Mains 3/PE AC 230/240 V − operation with mains choke/mains filter
E82xV551K2C
6
18
15
14
4)
E82xV751K2C
10
16
15
14
4)
E82xV152K2C
15
14
15
14
4)
E82xV222K2C
15
2 x 16
20
2 x 14
4)
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV551K4C
6
18
15
14
4)
E82xV751K4C
6
18
15
14
4)
E82xV152K4C
10
16
15
14
4)
E82xV222K4C
10
16
15
14
4)
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV551K4C
6
18
15
14
4)
E82xV751K4C
6
18
15
14
4)
E82xV152K4C
10
16
15
14
4)
E82xV222K4C
10
16
15
14
4)
4)
Pin−end connector required
Operation with increased rated power
Operation at an increased rated power is not UL−certified.