Function library – Lenze E82xVxxxKxxxxx User Manual
Page 347

Function library
Free interconnection of digital signals
Free configuration of digital input signals
l
347
EDS82EV903 EN 3.0
IMPORTANT
Possible settings
Code
Selection
Lenze
Name
No.
C0411
v
Level inversion
− digital inputs
0
0
Level inversion switched off
l
By entering the sum of the
selected values you can invert
several inputs.
l
C0114 and C0411 are the same
l
The "Change over parameter
set" cannot be inverted!
1
E1 inverted
2
E2 inverted
4
E3 inverted
8
E4 inverted
16
E5 inverted
Only application I/O
32
E6 inverted
Only application I/O
64
T1/T2 inverted
Only connect potential−free
switches to T1/T2.
T1/T2 is active when the switch is
open.
Signal linkage
The internal digital signals are linked with an external signal source by entering the
selection figure of the external signal in the corresponding subcode of C0410. C0410 can
be different for the parameter sets.
Examples
ƒ
C0410/10 = 2
ð Terminal X3/E2 is the signal source for controller inhibit (CINH)
ƒ
C0410/15 = 32
ð CAN−IN1/word1, Bit 3 is the signal source for the DC injection
brake (DCB)
)
Note!
The process data input words CAN−IN1.W1, CAN−IN1.W2, CAN−IN2.W1 and
CAN−IN2.W2 can be defined as analog word or as digital word (16 bit). If you
link internal digital signals (C0410/x = 30 ... 105), they must be defined as
digital input words. Otherwise the controller would interpret the bit control
information incorrectly.
Signal level
ƒ
Terminals (X3/E1 ... X3/E6):
– HIGH = +12 V ... +30 V
– LOW = 0 V ... +3 V
ƒ
Process data input words:
– HIGH = bit logic 1
– LOW = bit logic 0
ƒ
Response times: 1.5 ... 2.5 ms