beautypg.com

Sequence mode setting (:seq:mod), Sequence jump setting (:seq:step) – GW Instek PSB-2000 Series User Manual User Manual

Page 126

background image

PSB-2000 Series User Manual

126

Sequence Mode Setting (:SEQ:MOD)

This command controls a sequence operation. It can start, stop or
pause a sequence.

Setting

:SEQ:MOD
is as shown below:
0: Stops sequence operation.
1: Pause sequence operation – Waits for start.
2: Runs sequence operation (Executes sequence).

Application
example

:SEQ:MOD 2
Runs the sequence.

Query

:SEQ:MOD?
Inquires about the setting.

Response
example

2
Indicates that sequence operation is being executed. This
command causes an error if the sequence function is
running.

Remark

None

Sequence Jump Setting (:SEQ:STEP)

This command jumps to a specified step in the sequence operation.

Setting

:SEQ:STEP
The range is from 0 to 99.
This command can only be executed when a sequence is
paused.

Application
example

:SEQ:STEP 2
Jumps to step 2.

Query

:SEQ:STEP?
Inquires about the setting.

Response
example

2,1
Indicates that step 2 is selected and the repetition
frequency is 1(looped one time).

Remark

This command causes an error if the sequence function is
running.