Burkert Type 8717 User Manual
Page 82

82
Annex
9.1.7.
Bit field Binary OuT via BuS
Bit field Binary Out via BuS
Bit 0
activate > Power LEd
Bit 1
activate > Communication LEd
Bit 2
activate > Limit LEd
Bit 3
activate > Error LEd
Bit 4
activate BinOut 1 / activates binary output 1 (BinOut 1)
Bit 5
activate BinOut 2 / activates binary output 2 (BinOut 2)
Bit 6
RESERVEd
Bit 7
RESERVEd
Bit 8
RESERVEd
Bit 9
RESERVEd
Bit 10
RESERVEd
Bit 11
RESERVEd
Bit 12
RESERVEd
Bit 13
RESERVEd
Bit 14
RESERVEd
Bit 15
RESERVEd
9.1.8.
errOr aT SenSOr FaulT
The following functions are available for selection:
Close valve completely
The valve is closed completely. The set-point value settings is not taken into
consideration.
Open valve completely
The valve is closed opened. The set-point value settings is not taken into
consideration.
Setpoint controls duty
cycle 0 – 100 %
The set-point value settings controls the valve duty cycle. For example, a 10%
set-point value default wouldset a valve duty cycle of 10%.
Setpoint controls duty
cycle according to
last autotune
The set-point value controls the valve duty cycle as a percentage in the valve
working range determined by AutoTune.
Safety value controls
duty cycle 0 – 100 %
The safety value saved in the device (0 –100%) controls the valve duty cycle
directly.
Safety value controls
duty cycle according
to last autotune
The safety value saved in the device (0 – 100%) directly controls the valve duty
cycle as a percentage in the valve working range determined by AutoTune.
english
MFC Family