Burkert Type 0282 User Manual

Operating instructions type 0282

background image

Operating Instructions

Type 0282

Recorder No.

Voltage / Frequency / Power Consumption

Maximum Pressure

Marking (example):

Body Material
BR

=

Brass

SS

=

Stainless Steel

Seal Material
EPDM

=

EPDM

NBR

=

NBR

FKM

=

FKM

Circuit function
A

=

Normally Closed

B

=

Normally Open

Operating Instructions 0605/08_EU-EN_00893142

Approvals
The valve is either approved as

General Purpose valve for Hazardous Locations

Class I, Division 1, Group A, B, C, D
Class II, Division 1, Group E, F, G
Class III, Division 1 and 2
Operating Temperature T 4

or

FM approved as

Nonincendive for Hazardous Locations
Class I, Division 2, Group A, B, C, D
Class II, Division 2, Group F, G
Class III, Division 1 and 2
Operating Temperature T 4A

or

UL listed for Ordinary locations

or

CSA approved for Ordinary locations

See label on the valve.

Design:
2-way solenoid valve, direct acting, normally closed (Circuit
function A) or normally open (Circuit function B).

Seal Materials and Fluids handled:
See Table.

Fluid and Ambient Temperature:
For Hazardous Locations Div. 1 (T4 rated)
Max. Ambient Temperature

104 °F (40 °C)

Max. Fluid Temperature

194 °F (90 °C)

For Hazardous Locations Div. 2 and Ordinary Locations:
See Table.

Pressure Range:
Minimum pressure differential between and outlet port is 3 PSI.
Maximum inlet pressure see label on valve.

Installation:
Before installing valve ensure that piping etc. is free of foreign
matter (metal fillings, seal material, welding scale etc.). PTFE
tape is recommended for sealing ports. Arrow on valve body
gives flow direction. Installation as required but preferably
with coil uppermost. Installation in this position tends to
prevent foreign matter remaining in pilot valve (increased
life). A strainer upstream of valve, protects against effects of
foreign matter. Do not put any loads on coil unit. Pipework
should be supported such that valve body is not under strain.
Do not allow a pipe-end or sealing material to block the pilot
bore within the valve outlet. Inlet and outlet of valve must be
fullbore and pipework unrestricted.

Seal Materials

Fluid

Temperatures [° F]

Buna „N‰

Ethylene
Propylene

FKM

Air

Fluid T.

Ambient

+ 32 to + 194
+ 14 to + 130

- 22 to + 194
+ 14 to + 130

+ 14 to + 194
+ 14 to + 130

Water

Fluid T.

Ambient

+ 50 to + 194
+ 32 to + 130

+ 50 to + 194
+ 32 to + 130

+ 50 to + 194
+ 32 to + 130

Neutral Gas

Fluid T.

Ambient

+ 32 to + 194
+ 14 to + 130

- 22 to + 194
+ 14 to + 130

+ 14 to + 194
+ 14 to + 130

Light oil

Fluid T.

Ambient

+ 50 to + 194
+ 14 to + 130

+ 50 to + 194
+ 14 to + 130

LP-gas

Fluid T.

Ambient

+ 32 to + 140
+ 14 to + 130

+ 14 to + 140
+ 14 to + 130

Voltage 12V or 24V

UL / UR valid with

class 2 power supply only