Starting up the Modbus
register
address in
mfc
number of
registers
Designation / Description
r/w
format
0011
1
Baudrate
defines the baud rate of the Modbus communication
Value Baud rate
0
300
1
600
2
1200
3
2400
4
4800
5
9600
6
19200
7
38400
8
57600
9
115200
Attention please:
• A changed value will be active after a device reset.
• This register is available from firmware version
A.00.96.
R/W
UINT8
0012
1
Parity
defines the parity bit of the Modbus communication
Value Parity
0
nOne
1
Odd
2
EVEN
Attention please:
• A changed value will be active after a device reset.
• This register is available from firmware version
A.00.96.
R/W
UINT8
0013
1
Stopbit
defines the number of stop bits of the Modbus
communication.
Value Number of Stop bit
1
1 Stop bit
2
2 Stop bits
Attention please:
• A changed value will be active after a device reset.
• This value will be stored non volatile from firmware
version A.01.00.
R/W
UINT8