See “bit field others – Burkert Type 8717 User Manual
Page 80

80
Annex
9.1.3.
Bit field OTherS
Bit field OtherS
Bit 0
Power on / device power supply is on
Bit 1
Autotune active
Bit 2
Gas 1 active
Bit 3
Gas 2 active
Bit 4
Batch process active
Bit 5
BinIn 1 active / binary input 1 active
Bit 6
BinIn 2 active / binary input 2 active
Bit 7
BinIn 3 active / binary input 3 active
Bit 8
Set BinOut via Bus
Bit 9
Set to safety value / safety value active
Bit 10
Profile active
Bit 11
Valve control active
Bit 12
Close valve function active
Bit 13
Open valve function active
Bit 14
Valve hold function active
Bit 15
RESERVEd
9.1.4.
Bit field leDs
Bit field leDs
Bit 0
Communication active
Bit 1
MFIBusstatusNotActive / no cyclical data traffic active
Bit 2
MFIBusstatusPdActive / device is properly connected
Bit 3
MFIBusstatusPrmError / error in parameter telegram
Bit 4
MFIBusstatusCfgError / error in configuration telegram
Bit 5
MFIBusstatusNoMaster / no connection to the master
Bit 6
MFIBusstatusSdOnly / There is an explicit messaging connection to the master.
Acyclical communication only
Bit 7
MFIBusstatusTimeout / a timeout error has been detected
Bit 8
MFIBusstatusCriticalError / A critical error has been detected (for example double
address configuration on the slave).
Bit 9
RESERVEd
Bit 10
RESERVEd
Bit 11
RESERVEd
Bit 12
RESERVEd
Bit 13
RESERVEd
Bit 14
RESERVEd
Bit 15
RESERVEd
english
MFC Family