Burkert Type 8717 User Manual
Page 74
74
Starting up the Modbus
register
address in
mfc
number of
register
name / Description
r/w
type
0014
1
Controller Function
defines the behavior of the set-point setting
0: Normal operation of the controller and binary input controls
the valve
3: Hold function active for control output to the valve
22: off / closed
23: on / open -flow is restricted by the pressure and orifice of
the valve
64: Valve control output is controlled by the set-point value.
The min. and max. ramp up and down times (ramps, etc.)
apply.
Read only
65: Similar to 64, except that the percentage entry for the
control output is only within the working range of the valve
66: Calibration mode active
67: Autotune mode active
68: Safety mode active
R/W
UINT16
0015
1
Baudrate
Returns the Speed for Modbus Communication.
Value Baudrate
0
300
1
600
2
1200
3
2400
4
4800
5
9600
6
19200
7
38400
8
57600
9
115200
Attention please:
• A changed value will be active after a device reset..
R/W
UINT16
0016
1
Parity
defines the parity bit of the Modbus communication.
Value Parity
0
nOne
1
Odd
2
EVEN
Attention please:
• A changed value will be active after a device reset..
R/W
UINT16
english