Starting up the Modbus

register
address in
mfc

number of
register

name / Description

r/w

type

0014

1

Controller Function
defines the behavior of the set-point setting

0: Normal operation of the controller and binary input controls
the valve
3: Hold function active for control output to the valve
22: off / closed
23: on / open -flow is restricted by the pressure and orifice of
the valve
64: Valve control output is controlled by the set-point value.
The min. and max. ramp up and down times (ramps, etc.)
apply.

Read only
65: Similar to 64, except that the percentage entry for the
control output is only within the working range of the valve
66: Calibration mode active
67: Autotune mode active
68: Safety mode active

R/W

UINT16

0015

1

Baudrate
Returns the Speed for Modbus Communication.

Value Baudrate
0

300

1

600

2

1200

3

2400

4

4800

5

9600

6

19200

7

38400

8

57600

9

115200

Attention please:

• A changed value will be active after a device reset..

R/W

UINT16

0016

1

Parity
defines the parity bit of the Modbus communication.

Value Parity
0

nOne

1

Odd

2

EVEN

Attention please:

• A changed value will be active after a device reset..

R/W

UINT16

english