Burkert Type 8717 User Manual
Page 32
32
PROFIBUS DP Start-up
4.5.
explanation of variables used in cyclic data traffic
process data
explanation
identifier
Actual value
Actual value
(1 word = 2 bytes)
Value range 0 – 1000
41,40,00 (HEX); PdI
Set-point
Set-point value
(1 word = 2 bytes)
Value range 0 – 1000
41,40,01 (HEX); PdI
81,40,01 (HEX); PdO
Active gas
(used gas type)
whose calibration curve is used for control:
gas 1 or gas 2
(1 word = 2 bytes)
Value range 0 – 1
41,40,02 (HEX); PdI
Nominal flow Gas 1
Nominal flow in Nl/min of
calibration for gas 1
float = 4 bytes
41,83,03 (HEX); PdI
Nominal flow Gas 2
Nominal flow in Nl/min of
calibration for gas 2
float = 4 bytes
41,83,04 (HEX); PdI
Status limits
Read only
Bit field for states of device-internal threshold value:
(1 word = 2 bytes)
see “9.1. description of bit fields”
min. value 0, max. value 65535
41,40,05 (HEX); PdI
Status errors
Read only
Bit field for device errors that are present.
(1 word = 2 bytes)
see “9.1. description of bit fields”
min. value 0, max. value 65535
41,40,06 (HEX); PdI
Status others
Read only
Bit field for current states in the controller.
(1 word = 2 bytes)
see “9.1. description of bit fields”
min. value 0, max. value 65535
41,40,07 (HEX); PdI
Status LEds
Read only
Bit field for communication states.
(1 word = 2 bytes)
see “9.1. description of bit fields”
min. value 0, max. value 65535
41,40,08 (HEX); PdI
Status binary outputs
Reserved bit field
(1 word = 2 bytes)
see “9.1. description of bit fields”
41,40,09 (HEX) PdI
default values via bus
Bit field for states of LEds and binary outputs as they can
be assigned by the bus. To do this, the corresponding
functions must be configured in the device with the
PC program.
(1 word = 2 bytes)
see “9.1. description of bit fields”
41,40,0B (HEX); PdI
81,40,0B (HEX); PdO
english
MFC Family