CANopen Start-up

6.2.2.

Diagnostic object data

The diagnostic telegram consists of 8 bytes with the data shown in the following illustration:

diagnostic object data.

Byte

0

1

2

3

4

5

6

7

Table of

Contents

Emergency error code

(see “Table of diag-

nostic error”, page

42)

Error

register

(object

1001H)

Manufacturer-specific error field

The following two items are added to all errors:

Object 1001h: error register

name

Description of the input
data attribute

index, Subindex

Error register

All errors that occur on the
device are mapped
on this object.

dec: 4097, 0
Hex: 1001, 0

UNSIGNEd8

This object is an error register for the device. The device is able to represent internal errors in this byte.

This entry is mandatory for all devices. It is part of an emergency object.

Bit

m/O

Description

0

M

General error

1

O

Current

2

O

Voltage

3

O

Temperature

4

O

Communication error (overflow, error status)

5

O

device-specific

6

O

Reserved (always 0)

7

O

Manufacturer-specific

If a bit is set to 1, the specified error has occurred. The only mandatory error that must be indicated is a general