Burkert Type 8717 User Manual
Page 78

78
Starting up the Modbus
register
address in
mfc
number of
registers
Designation / Description
r/w
format
0010…0011 2
Totalizer
Totalizator in Nl units.
(0 °C / 1013mbar)
R
FLOAT32
0012…0019 8
Operating medium
R
8 x ASCII
character
0020
1
device type
Bürkert type number of the device
Min. value 0, max. value 65535
R
UINT16
0021…0022 2
device Ident Number
Bürkert identification number of the device
Min. value 0, max. value 99999999
R
UINT32
0023…0024 2
device Serial Number
Bürkert serial number of the device
Min. value 0, max. value 4294967295
R
UINT32
0025…0028 4
Version Number Software
see description of “Versions of the Software”
R
Ascii &
UINT8
0029
1
Modbus baud rate
Returns the Speed for Modbus Communication.
Value Baud rate
0
300
1
600
2
1200
3
2400
4
4800
5
9600
6
19200
7
38400
8
57600
9
115200.
R
UINT8
0030
1
Medium temperature
Temperature in 1/10 °C (231 = 23.1 °C)
R
UINT16
Versions of the Software
Returns 4 bytes, which are constructed as follows
X.YY.ZZ.CC
Ranges:
X
65 – 90 (‘A’ – ’Z’ ASCII)
YY
0 – 99
ZZ
0 – 99
CC 0 – 99
input register of list 1
Input registers aren’t supported while using Modbus register list 1.
Any read operation of input registers generates error “Illegal data Address”.
english
MFC Family