Profibus dp start-up, Address setting for bus devices – Burkert Type 8717 User Manual
Page 30
30
PROFIBUS DP Start-up
4.
prOFiBuS Dp STarT-up
4.1.
address setting for BuS devices
4.1.1.
Devices without rotary switch for address setting
The BUS address of devices can be set either with the Bürkert configuration tool MassFlowCommunicator in the
"Views" → "PROFIBUS/deviceNet/CANopen" view or directly with the BUS master.
After an address is changed, it must be initialized on the slave and also on the master. depending on the BUS, it
may be necessary to send an appropriate telegram.
To ensure the setting was made without problems, a device reset should be performed (turn the electrical
power off and back on).
4.1.2.
Devices with rotary switch for address setting
When the device is turned on, the address set as the slave address on the rotary switches is applied. Valid
addresses are:
• PROFIBUS 0 … 126
• deviceNet
0 … 63
• CANopen
1 … 127
If the address has been set outside the permissible range, the address setting has the validity as described in
section “4.1.1”.
LBS
Ones place, x 1
0 – 9
The number
multiplied by 1
→ 0 – 9
MBS
Tens place, x 10
0 – 9
The number
multiplied by 10
→ 0 – 90
A
→ 100
B
→ 110
C
→ 120
d
→ 130
E
→ 140
F
→ 150
Thus the address consists of LSB + MSB.
mSB
lBS
address
0
1
1
6
3
63
A
0
100
C
7
127
If you want to make an address setting with the BUS master and there are rotary switches available, set
the address to a value outside the valid range.
english
MFC Family