beautypg.com

Burkert Type 8717 User Manual

Page 61

background image

61

Acyclic Data Transfer with

PROFIBUS, DeviceNet and CANopen

Bürkert mfc family Object

name

Description of the input
data attributes

attribute address
(class, instance
attribute; data type)

Slot, index

index, Subindex

Dvn

Dpv1

canopen

y2_Limit1
Hyst

Read Write
Hysteresis for y2_Limit1 in
units per thousand
min. value 0, max. value 1000

dec: 110, 1, 23
Hex: 6E, 1, 17

UINT

dec: 1, 173
Hex: 1, Ad

dec: 12288, 23
Hex: 3000, 17

UNSIGNEd16

y2_Limit2

Read Write
Limit value for the second
threshold value from the
control output (y2) in units
per thousand
(only via MFCs)
min. value 0, max. value 1000

dec: 110, 1, 24
Hex: 6E, 1, 18

UINT

dec: 1, 174
Hex: 1, AE

dec: 12288, 24
Hex: 3000, 18

UNSIGNEd16

y2_Limit2
Hyst

Read Write
Hysteresis for y2_Limit2 in
units per thousand
min. value 0, max. value 1000

dec: 110, 1, 25
Hex: 6E, 1, 19

UINT

dec: 1, 175
Hex: 1, AF

dec: 12288, 25
Hex: 3000, 19

UNSIGNEd16

Gas1
Totalizer
Limit1

Read Write
Limit value for the first
threshold value of the
totalizer for gas1 in Nl/min
min. value 0,
max. value 1.00E+39

dec: 110, 1, 26
Hex: 6E, 1, 1A

REAL

dec: 1, 176
Hex: 1, B0

dec: 12288, 26
Hex: 3000, 1A

REAL32

Gas1
Totalizer
Limit2

Read Write
Limit value for the second
threshold value from the
totalizer for gas1 in Nl/min
min. value 0,
max. value 1.00E+39

dec: 110, 1, 27
Hex: 6E, 1, 1B

REAL

dec: 1, 177
Hex: 1, B1

dec: 12288, 27
Hex: 3000, 1

BREAL32

Gas2
Totalizer
Limit1

Read Write
Limit value for the first
threshold value of the
totalizer for gas2 in Nl/min
min. value 0,
max. value 1.00E+39

dec: 110, 1, 28
Hex: 6E, 1, 1C

REAL

dec: 1, 178
Hex: 1, B2

dec: 12288, 28
Hex: 3000,1C

REAL32

Gas2
Totalizer
Limit2

Read Write
Limit value for the second
threshold value from the
totalizer for gas2
in Nl/min
min. value 0,
max. value 1.00E+39

dec: 110, 1, 29
Hex: 6E, 1, 1d

REAL

dec: 1, 179
Hex: 1, B3

dec: 12288, 29
Hex: 3000, 1d

REAL32

english