Page 35

35
DeviceNet Start-up
5.2.
Configuration of process Data
5 static input and 2 static output assemblies can be selected to transmit process data via an I/O connection.
These assemblies contain selected attributes combined into one object so that process data can be transmitted
collectively via an I/O connection.
The process data is selected by setting the device parameters
Active Input Assembly and Active Output
Assembly or - if supported by the deviceNet-Master/Scanner - by setting Produced Connection Path and
Consumed Connection Path when an I/O connection is initialized according to the deviceNet specification.
assembly Object general
name
Description of the input data attributes
attribute address
(class, instance
attribute, data type)
ASS_NumberOfObjects
4, x, 1
ASS_Memberlist
4, x, 2
ASS_data
4, x, 3
assembly Object
Direction data
Description of data attributes
attribute address
(class, instance
attribute, data type)
Input / output
Not active
4, 0, 3
Input
Status byte + Flow(INT)
4, 2, 3
Input
Statusbyte + Flow(INT) + Setpoint(INT)
+ ActuatorOverrideByte + ValvedutyCycle(INT)
4, 6, 3
Output
Setpoint(INT)
4, 7, 3
Output
ActuatorOverrideByte + Setpoint(INT)
4, 8, 3
Input
Flow + status errors
4, 21, 3
Input
Flow + status errors + status limits
4, 22, 3
Input
Flow + status errors + status limits + status others
4, 23, 3
5.3.
acyclic data
See “7. Acyclic data Transfer with PROFIBUS, deviceNet and CANopen”
english
MFC Family