Configuration of process data, Acyclic data – Burkert Type 8717 User Manual

Page 35

background image

35

DeviceNet Start-up

5.2.

Configuration of process Data

5 static input and 2 static output assemblies can be selected to transmit process data via an I/O connection.
These assemblies contain selected attributes combined into one object so that process data can be transmitted
collectively via an I/O connection.

The process data is selected by setting the device parameters

Active Input Assembly and Active Output

Assembly or - if supported by the deviceNet-Master/Scanner - by setting Produced Connection Path and
Consumed Connection Path when an I/O connection is initialized according to the deviceNet specification.

assembly Object general

name

Description of the input data attributes

attribute address
(class, instance
attribute, data type)

ASS_NumberOfObjects

4, x, 1

ASS_Memberlist

4, x, 2

ASS_data

4, x, 3

assembly Object

Direction data

Description of data attributes

attribute address
(class, instance
attribute, data type)

Input / output

Not active

4, 0, 3

Input

Status byte + Flow(INT)

4, 2, 3

Input

Statusbyte + Flow(INT) + Setpoint(INT)
+ ActuatorOverrideByte + ValvedutyCycle(INT)

4, 6, 3

Output

Setpoint(INT)

4, 7, 3

Output

ActuatorOverrideByte + Setpoint(INT)

4, 8, 3

Input

Flow + status errors

4, 21, 3

Input

Flow + status errors + status limits

4, 22, 3

Input

Flow + status errors + status limits + status others

4, 23, 3

5.3.

acyclic data

See “7. Acyclic data Transfer with PROFIBUS, deviceNet and CANopen”

english