CANopen Start-up

process data

explanation

identification

default values via bus Bit field for states of LEds and binary outputs if

they can be assigned by the bus.
To do this, the relevant functions must be con-
figured in the device with the PC program.

(1 word = 2 bytes)
see “9.1. description of bit fields”

Tx (send)

dec: 12288, 12
Hex: 3000, C

UNSIGNEd16

Totalizer value Gas 1

Totalizer value of calibration for gas 1 in Nl.
Float = 4 bytes

RX (receive)

dec: 12288, 13
Hex: 3000, d

REAL32

Totalizer value Gas 2

Totalizer value of calibration for gas 2 in Nl.
Float = 4 bytes

RX (receive)

dec: 12288, 14
Hex: 3000, E

REAL32

Actual value as float

Actual value as Float (4 bytes)
Value range 0 – 1000

Other units can be parameterized by the value
of the flow unit from the “7.4. S-Analog Sensor
Object”.

e.g. units per thousand, Nl/min and the calibrated
unit

Tx, Rx

dec: 8960, 3
Hex: 2300, 3

REAL32

Set-point as float

Set-point value as Float (4 bytes)
Value range 0 – 1000

Other units can be parameterized by the value of
the flow unit from the “7.6. S-Single Stage Con-
troller Object”.

e.g. units per thousand, Nl/min and the calibrated
unit

RX (receive)

dec: 8448, 4
Hex: 2100, 4

REAL32

AddMeasureValue

Read only
Additional value as float (4 bytes)
Value as a percentage

This value is only supported by a few MFCs. If the
value is not supported, 0% is returned.

dec: 12288, 46
Hex: 3000, 2E

REAL32

Xp (currently not
supported)

Read only
Additional pressure value (2 bytes)
Value in units per thousand
Value range 0 – 1000

This value is only supported by a few MFCs. If the
value is not supported, 0% is returned.

dec: 12288, 47
Hex: 3000, 2F

UNSIGNEd16

english

MFC Family