Burkert Type 8717 User Manual
Page 49

49
CANopen Start-up
process data
explanation
identification
default values via bus Bit field for states of LEds and binary outputs if
they can be assigned by the bus.
To do this, the relevant functions must be con-
figured in the device with the PC program.
(1 word = 2 bytes)
see “9.1. description of bit fields”
Tx (send)
dec: 12288, 12
Hex: 3000, C
UNSIGNEd16
Totalizer value Gas 1
Totalizer value of calibration for gas 1 in Nl.
Float = 4 bytes
RX (receive)
dec: 12288, 13
Hex: 3000, d
REAL32
Totalizer value Gas 2
Totalizer value of calibration for gas 2 in Nl.
Float = 4 bytes
RX (receive)
dec: 12288, 14
Hex: 3000, E
REAL32
Actual value as float
Actual value as Float (4 bytes)
Value range 0 – 1000
Other units can be parameterized by the value
of the flow unit from the “7.4. S-Analog Sensor
Object”.
e.g. units per thousand, Nl/min and the calibrated
unit
Tx, Rx
dec: 8960, 3
Hex: 2300, 3
REAL32
Set-point as float
Set-point value as Float (4 bytes)
Value range 0 – 1000
Other units can be parameterized by the value of
the flow unit from the “7.6. S-Single Stage Con-
troller Object”.
e.g. units per thousand, Nl/min and the calibrated
unit
RX (receive)
dec: 8448, 4
Hex: 2100, 4
REAL32
AddMeasureValue
Read only
Additional value as float (4 bytes)
Value as a percentage
This value is only supported by a few MFCs. If the
value is not supported, 0% is returned.
dec: 12288, 46
Hex: 3000, 2E
REAL32
Xp (currently not
supported)
Read only
Additional pressure value (2 bytes)
Value in units per thousand
Value range 0 – 1000
This value is only supported by a few MFCs. If the
value is not supported, 0% is returned.
dec: 12288, 47
Hex: 3000, 2F
UNSIGNEd16
english
MFC Family