Starting up the Modbus

8.3.

Modbus register and communication objects

8.3.1.

Modbus register lists

Up to firmware A.00.99 only Modbus register list 0 is supported.

Started with firmware A.01.00 several register lists are supported for communication with the device. The default
list is 0. The register’s data description can be found in the specific documentation.

The selection of the used register list is made in the MassFlowCommunicator at the menu item „

Views HART /

Modbus COM settings” under „Modbus used register list“.

8.3.2.

holding register

These 16-bit values can be read and changed by the master.

Valid commands

code

name

Broadcast

0x03

Read Holding Register

No

0x06

Write Single Register

No

0x16

Write Multiple Register

No

Valid addresses

see below

holding register of register list 0 (default)

register
address in
mfc

number of
registers

Designation / Description

r/w

format

0001

1

Reset device
At a value of 1, the device is reset
Clearing the value is needless.

W

UINT16

0002

1

Reset Totalizator
At a value of 1 the value of the current totalizator is deleted.
Clearing the value is needless.

W

UINT16

0003

1

Set-point (in units per thousand)
Set-point value of gas flow rate / set-point value in per mill for
the active gas
min. value 0, max. value 1000

R/W

UINT16

0004

1

Active gas
Active Gas / calibration of this gas is used for control.

Value Gas
0

Gas 1

1

Gas 2

R/W

UINT16