Commands – Burkert Type 8717 User Manual
Page 12
12
Serial Communication
3.2.
Commands
command number
command name
0x00
readuniqueldentifier
request
Command
0x00
Byte count
0
data
-
response
Command
0x00
Byte count
14 (18)
Status
2 bytes, device status
data
12 (16) bytes
0
"254" (expansion)
1
manufacturer identification code
2
manufacturer‘s device type code
3
number of preambles required
4
universal command revision
5
device-specific command revision
6
software revision
7
hardware revision
8
device function flags
9 – 11
device Id number
1)
(12
common-practice command revision)
1)
(13
common tables revision)
2)
(14
data link revision)
2)
(15
device family code)
2)
Description
HART-Universal Command 0.
1)
First byte transferred: MSB
2)
Reserved for later versions
english
MFC Family