Burkert Type 0331 User Manual
Burkert Accessories for water
Operating Instructions
Type 0330/0331
Design:
2-way solenoid valve, direct acting, normally closed (Circuit func-
tion A), normally open (Circuit function B).
3-way solenoid valve, direct acting, normally closed (Circuit func-
tion C), normally open (Circuit function D), mixer function (Circuit
function E) or diverter function (Circuit function F).
Seal Materials and Fluids handled:
See Table1.
Fluid and Ambient Temperature:
For Hazardous Locations Div. 1 (T4 rated)
Max. Ambient Temperature
104 °F (40 °C)
Max. Fluid Temperature
194 °F (90 °C)
For Hazardous Locations Div. 2 and Ordinary Locations:
See Table1.
Pressure Range:
Maximum inlet pressure see label on valve.
Type 0330: PTFE tape is recommended for sealing ports.
Mounting is accomplished by means of four M4 x 8 mm tapped
holes located on the valve underside.
Type 0331: Ports A (B) are coded on side of body. For common
pressure, align "A(B)" markings on valve and manifold. Valve ope-
ration C an D valves can be mounted on the same manifold but the
manual override buttons will point in opposite directions.
To remove valve from manifold loosen only the two unsealed
screws. Manifolds can be connected together with nipples.
Blanking plugs, Order No. 0315-1016, should be screwed into
the unused ports. Manifolds can be fixed in position using M5
screws.
Manual override:
The manual override can be retained in position if, after depressing
the button, it is turned in a clockwise direction.
Assembly instructions:
The conduit connector on the coil (4) must be supported against
torque during the assembly using appropriate tools (1) (i.e. pliers,
gripper...) (for example a gripper).
While tightening for example a fitting (3) into the conduit connec-
tor attention must be paid to the fact that a max. torque of 20Nm
(177lbf in) is not exceeded.
Marking (example):
Body Material
BR
= Brass
SS
= Stainless Steel
Seal Material
EPDM = EPDM
NBR
= NBR
FKM
= FKM
Circuit Function
A = 2-way - Normally Closed
B = 2-way - Normally Open
C = 3-way - Normally Closed
D = 3-way - Normally Open
E = Mixer Function
F = Diverter Function
Recorder No.
Voltage / Frequency / Power Consumption
Maximum Pressure
Approvals
The valve is FM/CSA approved as
Explosion Proof valve for Hazardous Locations
Class I, Division 1, Group A, B, C, D
Class II, Division 1, Group E, F, G
Class III, Division 1 and 2
Operating Temperature T 4
or FM approved as
Nonincendive for Hazardous Locations
Class I, Division 2, Group A, B, C, D
Class II, Division 2, Group F, G
Class III, Division 1 and 2
Operating Temperature T 4A
CSA approved for Ordinary Locations
UL Recognized and UL Listed for General
Purpose and Fire Protection Services.
See label on the valve.
Operating Instructions 1103/13_EU-EN_00893144
Seal materials
Fluid
Temperatures [°F]
NBR
EPDM
FKM
Air
Fluid
Ambient
+ 32 to + 176
+ 32 to + 131
- 22 to + 194
+ 14 to + 131
+ 32 to + 194
+ 32 to + 131
Water
Fluid
Ambient
+ 41 to + 176
+ 32 to + 131
+ 41 to + 194
+ 14 to + 131
+ 41 to + 194
+ 32 to + 131
Neutral gas
Fluid
Ambient
+ 32 to + 176
+ 32 to + 131
- 22 to + 194
+ 14 to + 131
+ 32 to + 194
+ 32 to + 131
Light oil
Fluid
Ambient
+ 32 to + 140
+ 32 to + 131
+ 32 to + 140
+ 32 to + 131
LP-gas
Fluid
Ambient
+ 32 to + 140
+ 32 to + 131
+ 32 to + 140
+ 32 to + 131
Voltage 12V or 24V
UL / UR valid with
class 2 power supply only