Burkert Type 8693 User Manual
Page 99
99
Start-up and operation of the
position controller Type 8692
Procedure:
→
To input the characteristic points (function values), select the
FREE sub-menu option using the arrow keys and
confirm by pressing the selection key on the right (SELEC).
Another sub-menu (
FREE) opens in which the individual nodes are listed (as %).
→
Select the individual nodes using the arrow keys and confirm by pressing the selection key on the right (INPUT) in
order to change the value in the
SET VALUE sub-menu.
ESC
OK
+
-
SET VALUE
y 0 -> : 0.0
%
0.0
This value (as %) is changed
with the arrow keys
Accept the set value
Return without
change
Previously set value
(as %)
Figure 48:
Display CHARACT FREE
→
Using the arrow keys (+/-), set the function value from 0 to 100 % and confirm by pressing the selection key
on the right (OK).
→
When all changes have been made, leave the sub-menu by pressing the selection key on the left (EXIT).
→
Press the selection key on the left again (EXIT) to return to the
CHARACT menu option.
Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.
english
Type 8692, 8693