beautypg.com

Burkert Type 8693 User Manual

Page 241

background image

241

General Rules (Appendix)

The controller parameters can then be calculated from K

krit

and T

krit

according to the following table.

Adjustment.of.the.parameters.according.to.ziegler.and.nichols

Controller.type

Adjustment.of.the.parameters

P controller

Kp = 0.5 K

krit

-

-

PI controller

Kp = 0.45 K

krit

Tn = 0.85 T

krit

-

PID controller

Kp = 0.6 K

krit

Tn = 0.5 T

krit

Tv = 0.12 T

krit

Table 69:

Adjustment of the parameters according to Ziegler and Nichols

The adjustment rules of Ziegler and Nichols have been determined for P-controlled systems with a time delay of
the first order and dead time. However, they apply only to controllers with a disturbance reaction and not to those
with a reference reaction.

english

Type 8692,8693

This manual is related to the following products: