56

Installation

15.5. rotating the positioner for

process valves belonging to series 26xx and 27xx

If the connecting cables or hoses cannot be fitted properly following installation of the process valve, the positioner
can be rotated contrary to the actuator.

Fastening screw (2x)

Pneumatic connection

Positioner

Actuator

Figure 26:

Rotating the positioner, series 26xx and 27xx

procedure

Loosen the pneumatic connection between the positioner and the actuator.

Loosen the fastening screws (hexagon socket wrench size 2.5).

Rotate the positioner into the required position.

note!

Too.high.torque.when.screwing.in.the.fastening.screw.does.not.ensure.protection.class.IP65./.IP67!

• The fastening screw may be tightened to a maximum torque of 0.5 Nm only.

Tighten the fastening screws hand-tight only (maximum torque: 0.5 Nm).

Re-attach the pneumatic connections between the positioner and the actuator. If required, use longer hoses.