Installation
15.5. rotating the positioner for
process valves belonging to series 26xx and 27xx
If the connecting cables or hoses cannot be fitted properly following installation of the process valve, the positioner
can be rotated contrary to the actuator.
Fastening screw (2x)
Pneumatic connection
Positioner
Actuator
Figure 26:
Rotating the positioner, series 26xx and 27xx
procedure
→
Loosen the pneumatic connection between the positioner and the actuator.
→
Loosen the fastening screws (hexagon socket wrench size 2.5).
→
Rotate the positioner into the required position.
note!
Too.high.torque.when.screwing.in.the.fastening.screw.does.not.ensure.protection.class.IP65./.IP67!
• The fastening screw may be tightened to a maximum torque of 0.5 Nm only.
→
Tighten the fastening screws hand-tight only (maximum torque: 0.5 Nm).
→
Re-attach the pneumatic connections between the positioner and the actuator. If required, use longer hoses.