Burkert Type 8693 User Manual
Page 142
142
Start-up and operation of the
position controller Type 8693
PVmax X *X
upper scaling value for the process actual value
The unit for the temperature and the position for the decimal point is transferred from the inputs of the
lower scaling value.
1. input the upper scaling value for the process actual value
Press the down arrow key (←) to highlight the individual positions with a dark background. Press the
up arrow key (+) to set the value.
Adjustment range: -200 ... 800
Measurement range of the Pt 100: -20 °C – 220 °C or -4 °F – 428°F
This setting specifies the reference range for the dead band of the process controller as well as for the
analogue feedback of the process actual value (option)
SP INPUT - Type of set-point value default (internal / external)
This function specifies whether the set-point value default
• internal:
is implemented by pressing the keys on the positioner or
• external:
is implemented via the unit signal input.
Factory setting:
internal
SP-INPUT
ENTER
SELEC
internal
Internal set-point value default by
pressing the keys on the positioner
EXIT
external
External set-point value
default via unit signal input
Figure 89:
Operating structure P.CONTROL - SP-INPUT
english
Type 8692, 8693