beautypg.com

Burkert Type 8693 User Manual

Page 161

background image

161

Start-up and operation of the

position controller Type 8693

The operating structure of the menu options

SP/CMD Input and PV Input is identical and is described in the

diagram below:

SELEC

ERROR off

EXIT

SAFEPOS

Signal fault detection inactive

Activate approach of safety
position (only possible if
ERROR on is selected in the
Selection menu)

SP/CMD Input

ENTER

ERROR on

ENTER

Signal fault detection active

SELEC

SafePos off

Approach of the safety
position is not active.

SafePos on

Approach of the safety
position is active.
Approach of the safety
position which is saved
in

SAFEPOS.

EXIT

PV Input

Figure 101: Operating structure SIG-ERROR-8693-SP-CMD-PV

If signal fault detection is activated, the respective fault is indicated on the display.
(see chapter entitled "50.1. Error messages on the display")

Safety.position.SAFEPOS on
When

SAFEPOS on is set, the following configurations may occur:

Active

SAFEPOS

menu option If a fault is detected, the actuator moves to the lower

SAFEPOS set position.

Inactive

SAFEPOS

menu option If a fault is detected, the actuator moves to the end position which it would specify in the isolated
state.

english

Type 8692, 8693

This manual is related to the following products: