PROFIBUS-DP
30.
elecTrical cOnnecTiOns
danGer!
Danger.-.electrical.voltage.in.the.equipment!
There is a serious risk of injury when reaching into the equipment.
• Before starting work, always switch off the power supply and safeguard to prevent re-activation!
WarninG!
Danger.-.improper.installation!
Improper installation may result in injuries as well as damage to the device and the area around it.
• Fluid and electrical installations may be carried out by authorised technicians only and with the appropriate
tools!
Danger.due.to.unintentional.activation.of.the.equipment!
Unintentional activation of the equipment during installation may result in injuries and damage.
• Take appropriate measures to prevent the equipment from being unintentionally activated.
→
For operation of the device always connect the 5-pole, inversely coded M12 round socket and the 4-pole M12
circular plug (supply voltage).
The connection module of Type 8692 and 8693 features a setscrew with nut which is used to connect the technical earth
(see diagram).
→
Connect the setscrew to a suitable earthing point.
To ensure electromagnetic compatibility (EMC), ensure that the cable is as short as possible (max. 30 cm,
Ø 1.5 mm
2
).
30.1. connection diagram Type 8692
Socket.M12,.5-pole
(inversely-coded)
(PROFIBUS-DP)
Function earth FE
1
2
3
4
Circular.plug.M12,.4-pole
Supply voltage
2
1
4
3
5
Figure 110: Connection PROFIBUS-DP - Type 8692
english
Type 8692, 8693