X0 - working point of the process controller – Burkert Type 8693 User Manual
Page 134

134
Start-up and operation of the
position controller Type 8693
X0 - Working point of the process controller
Operating point in rest state.
Factory setting: 0.0 %
+
-
X0 0.0%
X0 0.0%
INPUT
OK
39)
Adjustment range:
0 – 100 %
Figure 82:
Operating structure P.CONTROL - X0
The "Tables for customer-specific settings”
appendix contains a table "61. Set parameters of the process
controller" in which you can enter your parameters.
FILTER - Filtering of the process actual value input
The filter is valid for all process actual value types and has a low pass behaviour (PT1).
Factory setting: 0
+
-
FILTER 0
FILTER 0
INPUT
OK
39)
Adjustment range:
0 – 9
Figure 83:
Operating structure P.CONTROL - FILTER
Setting.in.10.stages
Setting
Corresponds to limit frequency (Hz)
Effect
0
10
Lowest filter effect
1
5
2
2
3
1
4
0.5
5
0.2
6
0.1
7
0.07
8
0.05
9
0.03
Largest filter effect
Table 34:
Setting of filter effect
39)
If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.
english
Type 8692, 8693