Start-up and operation of the

position controller Type 8692

procedure:

calibr. POS Calibrating.the.actual.value.display.POS (0.-.100.%):.....

In the

CAL. USER menu press the arrow keys to select the calibr. POS menu option and confirm with the

selection key on the right (ENTER).

Accept the minimum position:

Press the arrow keys to select the

POS lower X menu option and confirm with the selection key on the right

(INPUT).

Approach the minimum position of the valve using the arrow keys (OPN/CLS) and confirm this value by pressing
the selection key on the right (OK).

Accept the maximum position:

Press the arrow keys to select the

POS upper X menu option and confirm with the selection key on the right

(INPUT).

Approach the maximum position of the valve using the arrow keys (OPN/CLS) and confirm this value by pressing
the selection key on the right (OK).

calibr. INP Calibrating.the.position.set-point.value.(4.–.20.mA;.0.–.20.mA;.0.–.5.V;.0.–.10.V):..

In the

CAL. USER menu press the arrow keys to select the calibr. INP menu option and confirm with the selection

key on the right (ENTER).

Accept the minimum input signal (0 mA; 4 mA; 0 V):

Using the arrow keys, select the

INP (0 mA; 4 mA; 0 V) menu option and confirm with the selection key on the right

(INPUT).

Apply the minimum value of the unit signal on the input and confirm by pressing the selection key on the right (OK).

Accept the maximum input signal (20 mA; 5 V; 10 V):

Using the arrow keys, select the

INP (20 mA; 5 V; 10 V) menu option and confirm with the selection key on the right

(INPUT).

Apply the maximum value of the unit signal on the input and confirm by pressing the selection key on the right (OK).

copy FACTUSER resetting.the.settings.under.CAL.USER.to.the.factory.settings:.....

In the

CAL. USER menu select the copy FACTUSER menu option using the arrow keys and confirm with the

selection key on the right (ENTER).

Hold down the selection key on the right (RUN) (for approx. 3 seconds) until the countdown has elapsed.

english

Type 8692, 8693