Sp - scale - scaling of the position controller – Burkert Type 8693 User Manual
Page 143

143
Start-up and operation of the
position controller Type 8693
SP - SCALE - Scaling of the position controller
This function is indicated in the selection menu only if the external set-point value default
(external) has
been selected in the SP INPUT menu option.
The
SP-SCALE function assigns the values for the lower and upper process set-point value to the particular current
or voltage value of the unit signal.
+
←
SPmin 0.0
SPmin 0.0 bar
INPUT
OK
45)
Set the lower scaling value for
the process set-point value; the
value is assigned to the lowest
current or voltage value of the
unit signal.
SP SCALE
ENTER
EXIT
+
←
SPmax 100.0
SPmax 100.0 bar
INPUT
OK
45)
Set the upper scaling value for
the process set-point value; the
value is assigned to the highest
current or voltage value of the
unit signal.
Figure 90:
Operating structure P.CONTROL - SP-SCALE
procedure for setting the scaling values (in the example of the lower scaling value SPmin):
→
Press the right selection key (INPUT) to enter the input screen for
SPmin.
On the display the last digit of the value is highlighted with a dark background.
→
Press the up arrow key (+) to specify the individual digits of the value and switch to the next digit with the
down arrow key (←).
→
When all input values have been specified, confirm by pressing the right selection key (OK) and jump back to
the selection screen.
45)
If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.
english
Type 8692, 8693