PROFIBUS-DP

PDI:.Process.Data.Input...(from the positioner to the controller)

name

Description

Identifier

PDI:POS

Actual position (position)

Actual value of position controller as ‰. Value range 0 – 1000.
Values < 0 or > 1000 are possible if e.g. Autotune has not run
through correctly.

GSD file:

PDI:POS


Identifier (HEX): 41, 40, 00

PDI:CMD

Nominal position (command)

Set-point value of position controller as ‰. Value range 0
– 1000.

GSD file:

PDI:CMD

Identifier (HEX): 41, 40, 01

PDI:PV


PDI:SP

Process actual value (process value)

Actual value of process controller in physical unit (as set in the
menu

P.CO INP or P.CO SCAL), max. value range -999 – 9999,

depending on internal scaling

Process set-point value (setpoint)

Set-point value of process controller in physical unit (as set in the
menu

P.CO INP or P.CO SCAL), max. value range -999 – 9999,

depending on internal scaling

GSD file:

PDI:PV



Identifier (HEX): 41, 40, 02


GSD file:

PDI:SP



Identifier (HEX): 41, 40, 03

PDI:TEMP

Device temperature (temperature)

Temperature of 0.1 °C is measured on the CPU board by the
sensor,

Value range -550 (-55 °C) – +1250 (+125 °C)

GSD file:

PDI:TEMP

Identifier (HEX): 41, 40, 04

PDI:MODE

Operating mode (operation mode)

Operating mode:

0:

AUTO

10:

P.TUNE

1:

MANUAL

12:

BUSSAFEPOS

2:

XTUNE

9:

P.QLIN

GSD file:

PDI:MODE

Identifier (HEX): 41, 00, 05

PDI:ERR

Error

Indicates the number of the process value (output) which was not
written. The value is retained until it is deleted with

PDO:ERR.

HEX

14

PDO:CMD / SP

16

PDO:MODE

GSD file:

PDI:ERR

Identifier (HEX): 41, 00, 06

PDI:
PCONact

0: Position controller (8692)

1: Process controller (8693)

GSD file:

PDI:PCONact

Identifier (HEX): 41, 00, 0A

Table 45:

Process Data Input