PROFIBUS-DP
PDI:.Process.Data.Input...(from the positioner to the controller)
name
Description
Identifier
PDI:POS
Actual position (position)
Actual value of position controller as ‰. Value range 0 – 1000.
Values < 0 or > 1000 are possible if e.g. Autotune has not run
through correctly.
GSD file:
PDI:POS
Identifier (HEX): 41, 40, 00
PDI:CMD
Nominal position (command)
Set-point value of position controller as ‰. Value range 0
– 1000.
GSD file:
PDI:CMD
Identifier (HEX): 41, 40, 01
PDI:PV
PDI:SP
Process actual value (process value)
Actual value of process controller in physical unit (as set in the
menu
P.CO INP or P.CO SCAL), max. value range -999 – 9999,
depending on internal scaling
Process set-point value (setpoint)
Set-point value of process controller in physical unit (as set in the
menu
P.CO INP or P.CO SCAL), max. value range -999 – 9999,
depending on internal scaling
GSD file:
PDI:PV
Identifier (HEX): 41, 40, 02
GSD file:
PDI:SP
Identifier (HEX): 41, 40, 03
PDI:TEMP
Device temperature (temperature)
Temperature of 0.1 °C is measured on the CPU board by the
sensor,
Value range -550 (-55 °C) – +1250 (+125 °C)
GSD file:
PDI:TEMP
Identifier (HEX): 41, 40, 04
PDI:MODE
Operating mode (operation mode)
Operating mode:
0:
AUTO
10:
P.TUNE
1:
MANUAL
12:
BUSSAFEPOS
2:
XTUNE
9:
P.QLIN
GSD file:
PDI:MODE
Identifier (HEX): 41, 00, 05
PDI:ERR
Error
Indicates the number of the process value (output) which was not
written. The value is retained until it is deleted with
PDO:ERR.
HEX
14
PDO:CMD / SP
16
PDO:MODE
GSD file:
PDI:ERR
Identifier (HEX): 41, 00, 06
PDI:
PCONact
0: Position controller (8692)
1: Process controller (8693)
GSD file:
PDI:PCONact
Identifier (HEX): 41, 00, 0A
Table 45:
Process Data Input
english
Type 8692, 8693