Output .(option), Configuring.the.outputs, Output (option) - configuring the outputs – Burkert Type 8693 User Manual
Page 162
162
Start-up and operation of the
position controller Type 8693
25.5. OUTPUT (option) -
configuring the outputs
The
OUTPUT menu option is only indicated in the selection menu of ADD.FUNCTION if the positioner has
outputs (option).
the outputs can be used for the following feedback signals:
Analogue output: Feedback of the current position (
POS), the position set-point value (CMD),
the process actual value (
PV) or the process set-point value (SP) to the control centre.
Binary outputs:
Alarm output for excessively large control deviations of the position controller or
for the output of the current position with respect to a specified limit position (> or <) or
for the output: actuator in safety position or
for the output of a sensor break or
for the output: operating state AUTOMATIC / MANUAL.
the positioner which has the outputs option is available in the following versions:
• one analogue output
• one analogue and two binary outputs
• two binary outputs
According to the version of the positioner only the possible adjustable outputs (
ANALOGUE, ANALOGUE +
BIN 1 + BIN 2 or BIN 1 + BIN 2) are indicated in the OUTPUT menu option.
OUTPUT
OUT ANALOG
OUT BIN2
EXIT
ENTER
ENTER
Configuration of the analogue output
OUT BIN1
Configuration of the binary output 1
Configuration of the binary output 2
Figure 102: Operating structure OUTPUT
english
Type 8692, 8693