. setting.the.proximity.switch.-.optional, Setting the proximity switch - optional – Burkert Type 8693 User Manual
Page 64
64
Installation
17.6. setting the proximity switch - optional
In the positioner with proximity switch option, the latter can be set to the bottom or the top end position.
danGer!
risk.of.electric.shock!
• Before reaching into the system, switch off the power supply and secure to prevent reactivation!
• Observe applicable accident prevention and safety regulations for electrical equipment!
Electronics module
Setting screw
Jumper
Home position jumper
Setting
bottom end position CFA and CFI
or
top end position CFB
Jumper set
Setting
top end position CFA and CFI
or
bottom end position CFB
Figure 30:
Setting the proximity switches
Procedure:
1. Open body and take off electronics module:
→
→
→→Disconnect supply voltage at the positioner and proximity switch connector.
→
Unscrew body casing (with transparent hood).
→
Remove electronics module.
english
Type 8692, 8693