Start-up and operation of the
position controller Type 8692
SELEC
OUT DEV.X
EXIT
Lim. DEV.X 1.0%
Selection: Alarm output for excessively large
control deviation of the position controller
OUT BIN 1
ENTER
OUT POS
Output: current position with respect to a specified
limit position
OUT Safepos
Output: actuator in safety position
OUT ERRSP/CMD
Output: sensor break
INPUT
+
-
Lim. DEV.X: 1.0
OK
31)
Input the limit value for the
permitted control deviation
Adjustment range:
1 ... 50 %
32)
Lim. POS 0%
INPUT
+
-
Lim. POS: 0
OK
31)
Input the limit position
Adjustment range:
0 ... 100 %
OUT BIN 1 type
ENTER
SELEC
normally opened
Selection of
switching
signal
EXIT
normally closed
OUT BIN 2
OUT BIN 2 type
OUT remote
Output: operating state MANUAL / AUTOMATIC
Figure 70:
Operating structure OUTPUT-BIN1
Normally closed output, in switched state low (≅→0 V)
Normally opened output, in switched state high (≅→24 V)
Changed values are not transferred into the memory (EEPROM) until the main menu (MAIN) is left.
31)
If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.
32)
The permitted control deviation Lim DEV.X XX must not be less than the dead band.