Start-up and operation of the
position controller Type 8692
22.3.15. CAL.USER
calibrating the actual value display and the inputs for the
position set-point value
The following points can be manually calibrated with this function:
• Position display (
POS) 0 – 100%
• Position set-point value display (
INPUT)
EXIT
calibr. POS
CAL. USER
ENTER
ENTER
OPN
CLS
POS lower 0
EXIT
POS lower 0
INPUT
OK
34)
OPN
CLS
POS upper 0
POS upper 0
INPUT
OK
34)
calibr. INP
ENTER
INP 4mA 0
EXIT
INP 4mA 0
35)
INPUT
OK
34)
INP 20mA 0
INP 20mA 0
35)
INPUT
OK
34)
copyFACT->USER
RUN
Pressfor
approx. 3
seconds
Reset the settings of
CAL.
USER
to factory settings
Figure 71:
Operating structure CAL.USER
Remove the
CAL.USER auxiliary function to re-activate the factory calibration.
34)
If the sub-menu is left by pressing the selection key on the left (ESC), the value remains unchanged.
35)
The signal type is displayed which is selected in the INPUT menu (4 – 20 mA; 0 – 20 mA; 0 – 5 V; 0 – 10 V).
english