Supply voltage (circular plug m12 - 4-pole), Option: with proximity switch - socket m8, 4-pole – Burkert Type 8693 User Manual
Page 61

61
Installation
17.3.2. Output signals to the control centre (e.g. plc) - circular
plug m12 - 8-pole (required for analogue output and/or
binary output option only)
→
Connect the pins according to the design (options) of the positioner.
Pin Wire.color
8)
Configuration
external.circuit./.signal.level
6
pink
Analogue position feedback + 6
5
GND
+ (0/4 - 20 mA or 0 - 5 / 10 V)
completely galvanically isolated
5
grey
Analogue position feedback
GND
4
yellow
Binary output 1
4
3
GND
24 V / 0 V
2
24 V / 0 V
3
green
Binary output 2
2
brown
Binary outputs GND
Table 16:
Pin assignment -Output signals to the control centre - circular plug M 12 - 8-pole
17.3.3. supply voltage (circular plug m12 - 4-pole)
Pin
Wire.color
9)
Configuration
External.circuit
1
brown
+ 24 V
1
3
24 V DC ± 10 %
max. residual ripple 10 %
2
not assigned
3
blue
GND
4
not assigned
Table 17:
Pin assignment - Supply voltage - (circular plug M 12 - 4-pole)
17.3.4. Option: with proximity switch - socket m8, 4-pole
Pin
Wire.color
10)
Configuration
External.circuit
1
brown
Proximity switch 1 out
3
1
2
Proximity switch
2
white
GND
3
blue
+ 24 V DC
4
not assigned
Table 18:
Pin assignment - proximity switch - socket M 8, 4-pole
When the supply voltage is applied, the positioner is operating.
→
Now implement the required basic settings and activate automatic adjustment of the positioner as described in
the chapter entitled “19. Initial start-up” or “Starting and setting up the position controller Type 8692”.
8)
The indicated colors refer to the connecting cable available as an accessory (919061)
9)
The indicated colors refer to the connecting cable available as an accessory (918038)
10)
The indicated colors refer to the connecting cable available as an accessory (92903475)
english